ZF10-145G(L)/T3150-40 Gas Insulated Switchgear


ZF10-145G(L)/T3150-40 Gas Insulated Switchgear

  1 Overview
  ZF10-145G(L) Gas Insulated Metal-Enclosed Switchgear (hereinafter referred as GIS) is appli-cable for the electrical system with features of three phases AC, 50HZ, and rated voltage of145kV.
  The GIS meets the relative requirements of national standard - GB7674-2008 and international standard IEC60517-1990. All the components inside the GIS conform to the corresponding national standard.
  2 Service and Installation Conditions
  Installation site: Indoor/outdoor
  Ambient temperature: -15℃~+40℃(indoor)/-30℃~+40℃(outdoor)
  Altitude: 1000m (No limitation for special order)
  Humidity:
  Relative humidity at average per day (25℃): ≤95%
  Relative humidity at average per month: ≤90%
  Wind speed: ≤35m/s (wind pressure ≤700Pa)
  Sunshine intensity:  0.1w/cm (at wind velocity of 0.5m/s)
  Icing thickness: 10mm
  Seismic intensity:
  Horizontal acceleration: ≤0.4g
  Vertical acceleration:≤0.2g
  Symmetrical Creepage distance: 25mm/kV (pollution class III), 31mm/kV (class IV)
  Keep the breaker away from places with combustible, explosive, corrosive materials and violent vibrations.